MCF-ENV-005 PUE Measurement
Claim operationAssurance level AL4Tier CP-3Evidence floor S3
Objective. Ensure power usage effectiveness is measured according to ISO/IEC 30134-2 with a declared measurement category, boundary and period, so that reported values are comparable, traceable and not distorted by metering gaps or boundary choices.
Requirement and evidence
The energy manager shall calculate PUE as annual total facility energy divided by annual IT equipment energy per ISO/IEC 30134-2, shall declare the measurement category and the metering points used for IT energy, shall include all energy sources (grid, on-site generation, fuel for generators), and shall report the value with category, period and data completeness.
Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E3 Operational and observational; E7 Derived and analytical. Optional: E5. Operating states: NORMAL.
MCF-ENV-006 Energy Allocation
Claim implementationAssurance level AL3Tier CP-2Evidence floor S3
Objective. Ensure energy consumed by shared infrastructure is allocated to tenants, clusters or services by a documented and metered method, so that per-capability energy and emissions are defensible.
Requirement and evidence
The energy manager shall define an allocation method for shared facility energy (cooling, losses, lighting, offices) to tenants or AI clusters, shall base allocation on sub-metered data wherever metering exists, and shall report unallocated energy below the declared threshold.
Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E7 Derived and analytical. Optional: E3. Operating states: NORMAL.
MCF-ENV-007 Efficiency Under Load
Claim operationAssurance level AL4Tier CP-3Evidence floor S3
Objective. Ensure facility efficiency is characterised across the load range actually experienced by AI deployments (partial occupancy during ramp-up, variable training load) and that heat reuse, where claimed, is measured.
Requirement and evidence
The energy manager shall report PUE or partial PUE at the declared IT load points, shall document the efficiency curves of major equipment (UPS, chillers, CDUs) at those points, and, where heat is exported for reuse, shall measure exported heat energy and report the energy reuse factor per ISO/IEC 30134-6.
Evidence required: E2 Configuration and technical state; E3 Operational and observational; E7 Derived and analytical. Optional: E1. Operating states: NORMAL.
MCF-ENV-008 Resilience-Efficiency Trade-Off
Claim designAssurance level AL2Tier CP-2Evidence floor S3Supports CG-05, CG-06, CG-14
Objective. Ensure that efficiency measures (UPS eco-mode, raised supply temperatures, reduced running redundant units, economiser hours, power capping) are evaluated for their effect on power and thermal resilience before adoption, so that efficiency gains do not silently consume resilience.
Requirement and evidence
The facility owner shall require a resilience impact assessment for every efficiency measure affecting power or cooling, reviewed by the electrical and mechanical engineers responsible for CG-05 and CG-06 evidence, stating the effect on transfer behaviour, ride-through, thermal ride-through time and redundancy in each declared operating state. The facility owner shall approve the measure under change control only when the assessment shows declared tolerances are still met.
Evidence required: E1 Documentary and declarative; E7 Derived and analytical. Optional: E4. Operating states: NORMAL, DEGRADED, EMERGENCY.