MCF-EVA-009 Decision Question
Claim designAssurance level AL2Tier CP-1Evidence floor S3Critical to CG-01
Objective. Ensure that each assessment answers a precisely stated decision question (for example 'Can Capability Instance X sustain training goodput within tolerance through loss of one CDU per pod, as of date D?') that names the Capability Instance, Service Outcomes, tolerances, operating states, intended users and prohibited interpretations.
Requirement and evidence
The decision authority shall approve, before fieldwork begins, a decision question for each assessment that states the Capability Instance, the Service Outcomes and tolerances in question, the operating states, the as-of date or period, the intended users and use, and the interpretations the conclusion shall not support. The lead assessor shall frame the assurance case top claim from the approved decision question and shall obtain re-approval if the question changes during the assessment.
Evidence required: E1 Documentary and declarative. Optional: E6. Operating states: NORMAL.
MCF-EVA-010 Scope and Criteria
Claim designAssurance level AL2Tier CP-2Evidence floor S3Critical to CG-02
Objective. Ensure that each assessment has an approved boundary (physical, logical, organisational, provider and temporal), applicable criteria (AIDCF artifact and capability-profile versions, applicable controls, claim types, gates), and visible exclusions with their residual effect.
Requirement and evidence
The lead assessor shall prepare, and the decision authority shall approve before fieldwork, a scope record for each assessment stating the boundary across physical, logical, organisational, provider and temporal dimensions; the operating states assessed; the applicable AIDCF artifact and capability-profile versions; the applicable controls with claim types; the applicable gates; and every exclusion with rationale and residual effect on the decision. The lead assessor shall reconcile the boundary to the ArchitectureSnapshot (MCF-CAP-004) and record any element of the snapshot that is neither in scope nor excluded.
Evidence required: E1 Documentary and declarative; E7 Derived and analytical. Optional: E2. Operating states: NORMAL.
MCF-EVA-011 Sampling and Testing
Claim implementationAssurance level AL3Tier CP-2Evidence floor S3Supports CG-04
Objective. Ensure that sampling is risk-based, reproducible and not over-extrapolated, and that tests are authorised, safe, defined in advance (initial state, method, expected result, abort criteria, restoration) and recorded with anomalies.
Requirement and evidence
The lead assessor shall document, for each sample, the population and its frame, strata, selection method, sample size rationale, exclusions and expansion rule, and shall record failed samples and their effect. For each test, the lead assessor shall obtain written authorisation from the system owner and, for hazardous or service-affecting tests, the safety authority, and shall record the initial state, method, expected result, abort criteria, instrumentation, restoration steps, result and anomalies. Tests shall be performed by authorised operators; assessors shall observe.
Evidence required: E1 Documentary and declarative; E3 Operational and observational; E4 Validation and test. Optional: E6. Operating states: NORMAL, MAINTENANCE, DEGRADED.
MCF-EVA-012 Specialist Involvement
Claim implementationAssurance level AL3Tier CP-2Evidence floor S3
Objective. Ensure that domain specialists (electrical, mechanical, compute, storage and network, OT security, resilience, evidence and data) approve the technical methods and conclusions in their domains, and that reliance on specialists is recorded with scope, competence and responsibility.
Requirement and evidence
The lead assessor shall identify, for each assessment, the domains requiring specialist judgement, appoint a competent specialist for each (MCF-GOV-023), and record the specialist's scope, competence evidence and responsibility. Each specialist shall approve the methods and the Control Assessment results in their domain. Where a specialist is external, the lead assessor shall evaluate their independence and the transferability of their conclusions.
Evidence required: E1 Documentary and declarative; E3 Operational and observational. Optional: E6. Operating states: NORMAL.