PHY Physical Site, Building and Security Infrastructure

6 families and 24 controls. Critical to CG-04 Life safety and hazardous energy, CG-09 Failure containment.

PHY domain guideSee it in the explorer

Proposed text. Requirements are from registry v1.1 (status CANDIDATE), proposed under amendment AMD-002. Intervals and thresholds are set by the assessed organisation in its capability profile. The approved v1.0 baseline uses the same identifiers.

24 controls

PHY-01 Site and location resilience

MCF-PHY-001 Site Hazard Assessment

Claim designAssurance level AL2Tier CP-1Evidence floor S3Supports CG-02, CG-03, CG-04

Objective. Establish that the natural and man-made hazards to which the site is exposed are identified, quantified against declared design levels and reflected in the design of facilities that host AI capability, so that no credible site-wide event exceeds the protection assumed by the architecture.

Requirement and evidence

The facility owner shall maintain a site hazard assessment, prepared or reviewed by competent specialists, that quantifies flood (fluvial, pluvial, coastal and groundwater), seismic, wind, lightning, extreme-temperature, wildfire and subsidence hazards at the declared design exceedance levels. The facility owner shall record, for each hazard, the design level adopted, the protective measures relied on and the residual exposure, and shall reassess the hazards when hazard mapping, climate projections or the site layout change.

Evidence required: E1 Documentary and declarative; E7 Derived and analytical. Optional: E5, E6. Operating states: NORMAL, EMERGENCY.

MCF-PHY-002 External Exposure

Claim designAssurance level AL2Tier CP-2Evidence floor S3Supports CG-09, CG-03

Objective. Ensure that threats and hazards originating outside the site boundary, including adjacent industrial activity, transport corridors, airspace, hostile vehicles and airborne contaminants, are characterised and mitigated so that they cannot disable redundant infrastructure together.

Requirement and evidence

The facility owner shall identify external exposures within a defined radius of the site, including major-accident-hazard installations, pipelines, rail and road corridors carrying hazardous goods, flight paths, high-voltage corridors and sources of smoke or corrosive emissions. The facility owner shall specify perimeter protection (stand-off, hostile vehicle mitigation, blast and intrusion resistance) proportionate to the assessed threat, and shall show that no single external event can impair both redundant utility intakes, both generator yards or all heat-rejection plant.

Evidence required: E1 Documentary and declarative; E7 Derived and analytical. Optional: E3, E5. Operating states: NORMAL, EMERGENCY.

MCF-PHY-003 Access and Logistics

Claim operationAssurance level AL4Tier CP-3Evidence floor S3Supports CG-10

Objective. Ensure that the site can receive the deliveries, emergency services and replacement equipment on which continuity and recovery of AI capability depend, including heavy dense racks, transformers and fuel, under normal and emergency conditions.

Requirement and evidence

The facility operator shall maintain a logistics and access plan that defines routes and constraints for fuel delivery, emergency services, rack-scale IT deliveries and replacement of the largest plant items (transformers, generators, chillers, CDUs). The facility operator shall verify that loading docks, lifts, corridors, ramps and doors along each route are rated for the mass and dimensions of the heaviest declared item, and shall maintain an alternative access route for fuel and emergency services when the primary route is obstructed.

Evidence required: E1 Documentary and declarative; E3 Operational and observational. Optional: E4, E6. Operating states: NORMAL, MAINTENANCE, EMERGENCY.

MCF-PHY-004 Adjacent Risk

Claim designAssurance level AL2Tier CP-1Evidence floor S3Supports CG-03

Objective. Ensure that risks arising from adjacent occupancies, shared structures and neighbouring tenants on the same campus or in the same building are identified and cannot propagate into the facility hosting the assessed capability.

Requirement and evidence

The facility owner shall identify adjacent occupancies and shared building elements (party walls, roofs, risers, plant rooms, car parks and loading areas) and the hazards they present, including fire load, water, vibration, vehicle impact and uncontrolled access. The facility owner shall agree with neighbouring occupiers or the landlord the separation, notification and emergency-coordination arrangements for each adjacent risk, and shall record any adjacent risk that cannot be controlled as an accepted risk with an accountable owner.

Evidence required: E1 Documentary and declarative. Optional: E6, E3. Operating states: NORMAL, EMERGENCY.

PHY-02 Building and structural integrity

MCF-PHY-005 Structural Capacity

Claim designAssurance level AL2Tier CP-2Evidence floor S3Supports CG-02, CG-04

Objective. Demonstrate that floor slabs, raised floors, roofs and supports can carry the loads imposed by dense AI racks, liquid-filled cooling systems, battery systems and rooftop heat-rejection plant, with margin, for the declared deployment.

Requirement and evidence

The facility owner shall hold a structural capacity statement from the structural engineer of record that states the uniformly distributed and concentrated load capacity of each data hall, plant room, battery room and roof area. The facility owner shall ensure the statement accounts for operating (wet) mass of liquid-cooled racks, CDUs, manifolds, coolant distribution pipework and immersion tanks, and shall require a structural re-check before any deployment that raises planned load above the declared utilisation threshold.

Evidence required: E1 Documentary and declarative; E7 Derived and analytical. Optional: E5. Operating states: NORMAL, MAINTENANCE.

MCF-PHY-006 Rack Loading

Claim implementationAssurance level AL3Tier CP-2Evidence floor S3Supports CG-04, CG-14

Objective. Ensure that as-installed rack positions do not exceed the floor, raised-floor and rack-frame ratings for the actual mass of installed equipment, including liquid in manifolds and cold plates.

Requirement and evidence

The facility operator shall maintain a rack-position load register recording the operating mass of every rack and the rated capacity of its position. The facility operator shall verify rack mass at installation for each new rack type, shall prevent installation where the position rating would be exceeded, and shall reconcile the register to installed equipment at the declared interval.

Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E3 Operational and observational. Optional: E7. Operating states: NORMAL.

MCF-PHY-007 Anchorage and Vibration

Claim implementationAssurance level AL3Tier CP-2Evidence floor S3Supports CG-09

Objective. Ensure that racks, CDUs, battery systems, tanks, switchgear and suspended services are restrained against seismic and operational loads, and that vibration from rotating plant does not degrade IT or storage equipment.

Requirement and evidence

The facility owner shall specify and install anchorage and bracing for racks, CDUs, battery cabinets, fuel and water tanks, switchgear, busway and overhead cable and pipe supports to the seismic design level determined in MCF-PHY-001. The facility operator shall isolate generators, chillers and pumps so that vibration transmitted to IT spaces remains within the most restrictive OEM limit for installed equipment, and shall verify installed anchorage by inspection at commissioning and after changes.

Evidence required: E1 Documentary and declarative; E3 Operational and observational. Optional: E4, E5. Operating states: NORMAL, EMERGENCY.

MCF-PHY-008 Building Envelope

Claim operationAssurance level AL4Tier CP-3Evidence floor S3Supports CG-06

Objective. Ensure the building envelope keeps water, wind-driven rain, dust and uncontrolled air out of IT and plant spaces and maintains the enclosure integrity on which gaseous suppression and air management depend.

Requirement and evidence

The facility operator shall inspect roofs, roof penetrations, gutters, façades, louvres and doors at the declared interval and after severe weather, shall correct defects within a risk-based period, and shall prohibit water-bearing services and roof drainage from passing over IT and electrical rooms unless they are contained and monitored.

Evidence required: E1 Documentary and declarative; E3 Operational and observational. Optional: E6. Operating states: NORMAL, EMERGENCY.

PHY-03 Physical zoning and segregation

MCF-PHY-009 Security Zones

Claim implementationAssurance level AL3Tier CP-2Evidence floor S3Supports CG-15, CG-09

Objective. Ensure that the site is divided into layered security zones whose protection increases towards the most critical assets, including power and cooling plant as well as IT halls, so that access to any asset that can disable AI capability requires passing proportionate barriers.

Requirement and evidence

The security manager shall define a zoning model with at least perimeter, building, secure-corridor, critical-space and rack/cage levels, and shall assign every critical asset (MV intake, switchgear, UPS and battery rooms, generator yard, fuel, heat rejection, CDU and pump rooms, meet-me rooms, data halls, control rooms) to a zone. The security manager shall ensure each zone boundary has physical barriers, access control and detection appropriate to the zone and that critical plant zones are protected no less than the IT halls they serve.

Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E3 Operational and observational. Optional: E5. Operating states: NORMAL, MAINTENANCE.

MCF-PHY-010 Fire Zones

Claim implementationAssurance level AL3Tier CP-4Evidence floor S4Critical to CG-09Supports CG-04

Objective. Ensure that fire compartmentation separates redundant power, cooling and network paths so that a single fire cannot disable both halves of a redundant system, and limits fire and smoke spread between IT, battery, electrical and plant spaces.

Requirement and evidence

The facility owner shall define fire compartments in the fire strategy so that A and B power paths, redundant UPS and battery rooms, redundant cooling plant and diverse network routes are in separate compartments or are protected by fire-rated enclosures of the declared rating. The facility operator shall maintain fire-stopping of every penetration through compartment boundaries and shall inspect a sample of penetrations at the declared interval and after works.

Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E3 Operational and observational. Optional: E5. Operating states: NORMAL, EMERGENCY.

MCF-PHY-011 Water Zones

Claim implementationAssurance level AL3Tier CP-2Evidence floor S3Supports CG-09, CG-04

Objective. Ensure that liquid-bearing systems, which are pervasive in liquid-cooled AI halls, are spatially and physically separated from electrical distribution and that any leak is contained, detected and drained before it reaches energised equipment.

Requirement and evidence

The facility owner shall define water zones identifying all spaces where water, glycol, dielectric fluid or refrigerant-bearing pipework is present. The facility owner shall locate or protect electrical switchgear, UPS, busway and PDUs so that a leak from any pipe, joint, CDU, manifold or quick-disconnect cannot reach them uncontained, using routing above or below with drip trays, bunding, falls to drains and zoned leak detection that alarms and, where declared, initiates isolation.

Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E3 Operational and observational. Optional: E4. Operating states: NORMAL, MAINTENANCE.

MCF-PHY-012 Tenant Segregation

Claim implementationAssurance level AL3Tier CP-2Evidence floor S3Supports CG-13, CG-02

Objective. Ensure that, in shared or colocation facilities, each tenant's equipment and the shared infrastructure serving it are physically segregated and that responsibility for shared elements is explicit.

Requirement and evidence

The facility provider shall physically segregate tenant spaces using cages, suites or dedicated halls with access restricted to authorised tenant personnel, and shall disclose to each tenant the shared infrastructure (power paths, cooling loops, meet-me rooms, risers) serving its space. The tenant shall map its capability to those shared elements and record provider and tenant responsibilities for each.

Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E6 Human and experiential. Optional: E3. Operating states: NORMAL, MAINTENANCE.

PHY-04 Access and surveillance

MCF-PHY-013 Identity-Based Access

Claim operationAssurance level AL4Tier CP-3Evidence floor S4Supports CG-15

Objective. Ensure physical access to critical zones is granted to identified individuals on a need basis, is promptly revoked, and is recorded so that every entry to a critical space can be attributed.

Requirement and evidence

The security manager shall operate a physical access control system that grants access to critical-space zones only to named individuals with approved business need, enforces multi-factor authentication at those zones, revokes access within the declared latency when a person leaves or changes role, and reviews critical-zone access rights at the declared interval. The security manager shall integrate leaver events from the authoritative HR or contractor source.

Evidence required: E2 Configuration and technical state; E3 Operational and observational. Optional: E1, E7. Operating states: NORMAL, MAINTENANCE, EMERGENCY.

MCF-PHY-014 Visitor Control

Claim operationAssurance level AL4Tier CP-3Evidence floor S3

Objective. Ensure that visitors, vendors and contractors, including OEM field engineers servicing accelerator systems, are identified, authorised, escorted and supervised in critical spaces.

Requirement and evidence

The security manager shall require pre-registration, identity verification and host approval for every visitor, shall issue time-limited credentials, and shall require escort in critical-space zones at no more than the declared visitor-to-escort ratio. The facility operator shall link contractor attendance in plant spaces to an approved work order or permit.

Evidence required: E3 Operational and observational. Optional: E1, E6. Operating states: NORMAL, MAINTENANCE.

MCF-PHY-015 Surveillance Coverage

Claim implementationAssurance level AL3Tier CP-2Evidence floor S3

Objective. Ensure video surveillance covers entries to critical zones, critical plant and high-value asset areas at an image quality sufficient for the declared purpose, with retention and integrity supporting investigation.

Requirement and evidence

The security manager shall define an operational requirement for each camera view stating its purpose (detect, observe, recognise or identify), shall install and maintain cameras to meet it, shall retain recordings for the declared period with integrity protection, and shall verify coverage after layout changes.

Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E3 Operational and observational. Operating states: NORMAL, MAINTENANCE.

MCF-PHY-016 Alarm Response

Claim effectivenessAssurance level AL5Tier CP-4Evidence floor S4

Objective. Demonstrate that intrusion, forced-door, held-door and tamper alarms at critical zones are acknowledged and physically attended within declared times, including at night and when many alarms occur together.

Requirement and evidence

The security manager shall define acknowledgement and attendance times for each alarm class in critical zones, shall staff and equip the response to meet them, and shall test response by unannounced exercises at the declared interval, including an exercise during concurrent facility alarms.

Evidence required: E2 Configuration and technical state; E3 Operational and observational; E4 Validation and test. Optional: E6. Operating states: NORMAL, EMERGENCY.

PHY-05 Asset movement and custody

MCF-PHY-017 Delivery Controls

Claim operationAssurance level AL4Tier CP-3Evidence floor S3

Objective. Ensure inbound deliveries of high-value AI hardware, storage media and critical spares are received against an expected manifest, inspected for tampering and held under custody until accepted.

Requirement and evidence

The facility operator shall receive critical deliveries only against an advance notice and purchase reference, shall inspect seals and packaging for tampering, shall record serial numbers at receipt and shall hold received items in a controlled store until they are accepted into the asset register.

Evidence required: E3 Operational and observational. Optional: E1, E2. Operating states: NORMAL.

MCF-PHY-018 Equipment Movement

Claim operationAssurance level AL4Tier CP-3Evidence floor S3Supports CG-04

Objective. Ensure movement of dense racks and heavy plant within the facility is planned, authorised and executed without exceeding route ratings, damaging live infrastructure or creating tip-over and crush hazards.

Requirement and evidence

The facility operator shall require a move plan, approved by the facilities engineer, for every movement of a rack or plant item above the declared mass threshold, stating route, route ratings, equipment (skates, tuggers, lifting), crew competence and proximity to live services. The facility operator shall drain or isolate liquid-cooled racks where the OEM requires it before movement.

Evidence required: E1 Documentary and declarative; E3 Operational and observational. Optional: E6. Operating states: NORMAL, MAINTENANCE.

MCF-PHY-019 Media Custody

Claim operationAssurance level AL4Tier CP-3Evidence floor S4

Objective. Ensure storage media holding training data, checkpoints or model weights are inventoried and in unbroken custody whenever they are removed from service, in transit, under repair or awaiting destruction.

Requirement and evidence

The facility operator shall maintain a serialised inventory of data-bearing media outside production service, shall record each custody transfer with time, person and location, shall store media in a controlled container or room, and shall reconcile the inventory at the declared interval. The data owner shall define which media classes require encryption verification before leaving the controlled store.

Evidence required: E2 Configuration and technical state; E3 Operational and observational. Optional: E1. Operating states: NORMAL, MAINTENANCE.

MCF-PHY-020 Decommissioning Custody

Claim operationAssurance level AL4Tier CP-3Evidence floor S4

Objective. Ensure that equipment leaving the facility at end of life, including accelerators, servers, storage and network devices, is sanitised or destroyed to the declared standard with verified certificates, and that decommissioning does not disturb live infrastructure.

Requirement and evidence

The facility operator shall decommission equipment only under an approved decommissioning work order that identifies the asset, its data-bearing components, dependent power and cooling connections and the sanitisation or destruction method. The facility operator shall obtain a certificate per serial from any third-party disposal provider and shall reconcile certificates to the decommissioning list.

Evidence required: E1 Documentary and declarative; E3 Operational and observational. Optional: E5. Operating states: NORMAL, MAINTENANCE.

PHY-06 Fire, life safety and emergency interfaces

MCF-PHY-021 Fire Detection

Claim effectivenessAssurance level AL5Tier CP-5Evidence floor S4Critical to CG-04Supports CG-09

Objective. Demonstrate that fire detection in IT, electrical, battery and plant spaces detects incipient fires early enough for safe evacuation and for controlled response before a fire disables redundant infrastructure, accounting for high airflow and liquid-cooled hall conditions.

Requirement and evidence

The fire safety manager shall provide detection designed for the airflow conditions of each space: very early warning aspirating smoke detection in high-airflow IT halls and electrical rooms, and off-gas or appropriate gas detection plus heat and smoke detection in lithium-ion battery rooms and enclosures. The fire safety manager shall test detection functionally at the declared interval, including smoke transport time for aspirating systems, and shall ensure alarms are received at a continuously staffed location.

Evidence required: E1 Documentary and declarative; E4 Validation and test; E5 Independent and third-party. Optional: E3. Operating states: NORMAL, MAINTENANCE.

MCF-PHY-022 Suppression Interfaces

Claim effectivenessAssurance level AL5Tier CP-5Evidence floor S4Critical to CG-04Supports CG-06, CG-07

Objective. Demonstrate that suppression systems and their interfaces with power, cooling, ventilation and control systems act as designed, so that suppression is effective without causing an avoidable loss of AI capability or an unsafe condition.

Requirement and evidence

The fire safety manager shall maintain a cause-and-effect matrix covering every interface between detection, suppression (sprinkler, pre-action, water mist, gaseous agent) and other systems, including HVAC shutdown, damper closure, CDU and pump behaviour, power isolation and door release. The fire safety manager shall test the matrix end to end at the declared interval, shall verify room integrity for gaseous systems by enclosure test, and shall confirm that fire-mode actions do not stop liquid cooling to unaffected areas unless the fire strategy requires it.

Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E4 Validation and test; E5 Independent and third-party. Optional: E3. Operating states: NORMAL, EMERGENCY.

MCF-PHY-023 Egress and Emergency Access

Claim operationAssurance level AL4Tier CP-5Evidence floor S4Critical to CG-04

Objective. Ensure occupants of data halls, plant rooms and battery rooms can escape safely and emergency responders can gain access, including in dense hot-aisle/cold-aisle containment, liquid-cooled halls with overhead manifolds and spaces protected by gaseous agents.

Requirement and evidence

The fire safety manager shall maintain egress routes from every occupied space within the travel distances of the fire strategy, shall ensure secured doors on escape routes release on fire alarm or by local override, shall provide pre-discharge warning and abort controls for gaseous systems, and shall provide emergency responders with plans, hazard information (batteries, refrigerants, coolants, arc-flash hazards) and access means.

Evidence required: E1 Documentary and declarative; E3 Operational and observational; E4 Validation and test; E5 Independent and third-party. Optional: E6. Operating states: NORMAL, EMERGENCY, MAINTENANCE.

MCF-PHY-024 Emergency Shutdown Governance

Claim effectivenessAssurance level AL5Tier CP-5Evidence floor S4Critical to CG-04Supports CG-07, CG-09

Objective. Ensure emergency power-off (EPO) and other emergency shutdown functions protect people and responders while being protected against inadvertent or malicious activation that would cause an uncontrolled shutdown of AI capability.

Requirement and evidence

The facility owner shall define the scope of each emergency shutdown function (EPO, battery disconnect, fuel shut-off, CDU emergency stop) and the authority to activate it. The facility operator shall protect activation devices against inadvertent operation (covers, two-action operation, location), shall verify by test at the declared interval that each function isolates exactly its declared scope, and shall review any activation as a significant incident.

Evidence required: E1 Documentary and declarative; E2 Configuration and technical state; E4 Validation and test; E5 Independent and third-party. Optional: E3. Operating states: NORMAL, EMERGENCY, MAINTENANCE.